官厅水库入库水生物接触A/O工艺试验 |
摘要点击 1753 全文点击 977 投稿时间:2002-11-09 修订日期:2003-01-06 |
查看HTML全文
查看全文 查看/发表评论 下载PDF阅读器 |
中文关键词 官厅水库 生物接触A/O工艺 进水氨氮负荷 |
英文关键词 Guanting Reservior bio-contact oxidation A/O process influent ammonia nitrogen loading |
|
中文摘要 |
试验表明,生物接触A/O工艺对官厅水库入库水中COD、氨氮等污染物有明显的去除效果,可以有效地改善官厅水库入库水的水质.在单位供气量(空气/氨氮)≥0.1L/mg,进水氨氮负荷≤0.08kg/(m3·d)的条件下,处理后出水COD稳定在30mg/L左右,氨氮去除率>60%,TN的去除率为1.0%~31.3%.进水氨氮负荷是主要的控制参数,应控制在≤0.08kg/(m3·d). |
英文摘要 |
The results of the experiments showed that biological contact A/O process had evident removal effect of contaminations such as COD、ammonia nitrogen in water entering into Guanting Reservior and could successfully resume the quality. Under the conditions that air supply flux(gas/ ammonia nitrogen)was more than 0.1L/mg and influent ammonia nitrogen loading was lower than 0.08kg/(m3·d), effluent COD was steadily 30mg/L around, ammonia nitrogen removal rate was higher than 60%, and TN removal rate was 1.0%~31.3%.The main control parameter was influent ammonia nitrogen loading, which was proposed to be lower than 0.08kg/(m3·d). |